Rated voltage
|
100V; 110V; 50Hz
|
| Rated current |
5A; 1A
|
|
Setting range of high limit U>/Un
|
0,90-1,20
|
|
Setting range of down limit U</Un
|
0,85-1,15
|
| Histeresis |
(1% Un)
|
| Setting range of compaundation voltage at
In |
(0-11%)Un
|
| Setting range of time delay |
20-120 sec.
|
| Voltage of blockade |
80% Un
|
| Voltage of deblockade |
85% Un
|
| Power drain from voltage path |
|
- at Un=100V
- at U=120V |
|
| Power drain from current path |
0,5 VA
|
Autonomous supply (from measuring supplied
path)
|
|
| Contacts |
|
| Max voltage |
250V
|
| Continuous current |
5A
|
| Breaking capacity at cos
j = 1 |
1000VA
|
| at DC current with L/R=40 ms |
20W
|
| Ambient temperature |
-10oC+50oC
|
| Test voltage |
2 kV; 50Hz; 1 min.
|
| Mass |
cca 5 kg
|